For on-site repair and support, call us at 1-704-448-2212 or email sales@qualitrol.com.
The GE-Emerson IC660BBA021 Genius RTD Input I/O Block has six input circuits, in three groups of two circuits each. Group to group isolation is 300 volts. Each input can be used with platinum, nickel, or copper RTDs. Input data for each circuit is linearized according to the type of RTD selected. Input data is reported to the CPU in engineering units of tenths of degrees Celsius, tenths of degrees Fahrenheit, tenths of Ohms, or counts. Additional configurable features include alarm thresholds, RTD resistance, alpha type, linearization, and input filter time.
RTD blocks are factory-calibrated; there is no need for subsequent recalibration. In addition, the block’s automatic diagnostics can pinpoint the cause of installation and run-time errors:
Fault reporting can be enabled or disabled circuit-by-circuit.
We're open Mo-Fr 8:00am to 5:00pm