Remanufactured

$861.80
$775.62
  • 3 in stock

Repair

Call for pricing
  • Usually ships in 3-5 business days

For on-site repair and support, call us at 1-704-448-2212 or email sales@qualitrol.com.

  • IC693MDL931RMN

Overview

Features

  • 24VDC, 120/240VAC, 50/60Hz rated voltage (nominal)
  • Output voltage range:
    • 5 to 30VDC
    • 5 to 250VAC, 50/60Hz
  • Isolation:
    • 1,500V between field side and logic side
    • 500V between groups
  • Maximum load:
    • 8 Amps resistive max. per output
    • 20 Amps max. per module for UL installations
  • 10mA minimum load
  • 8 Amps max. inrush current for one cycle
  • 15ms On and Off response time
  • 1mA max. output leakage current at 250VAC (77°F)
  • Internal power consumption:
    • 45mA (all outputs on) from 5V bus on backplane
    • 100mA (all outputs on) from relay 24V bus on backplane

Description

The GE-Emerson IC693MDL931 8 Amp Isolated Relay Output Module can control a wide range of user-supplied load devices, such as motor starters, solenoids, and indicators. The user must supply the AC or DC power to operate the field devices connected to this module. There are no fuses on this module.

LED indicators that provide each point's ON/OFF status are located at the top of the module. The LEDs are arranged in two horizontal rows with eight green LEDs in each row. This module uses the top row labeled A1 through 8 (points 1 through 8) for output status; the bottom row is not used and the fuse LED is not used. An insert goes between the inside and outside surfaces of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information, and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is color-coded red to indicate a high-voltage module. This module can be installed in any I/O slot of a 5 or 10-slot baseplate in a Series 90-30 PLC system.