  • IC660BBD110RMN

Overview

Features

  • Unit OK, I/O Enabled LEDs (I/O Block)
  • LEDs (each circuit) reflect state of input (logic side)
  • 1,500V input to ground or serial bus isolation
  • 28W max. heat dissipation with 16 inputs on at full current
  • 93 to 132VAC operating voltage (single source)
  • 47 to 63Hz frequency
  • 80mA max. block current plus 200mA max. input circuit current required power (block only)
  • 5 Amps terminal board rating (input or feed-through current)
  • 1 cycle power supply dropout time (16.7ms at 60Hz, 20ms at 50Hz)

Description

The GE-Emerson IC660BBD110 Genius Discrete Input Block provides an interface to 115VAC discrete input sensors. Typical inputs to this block are contact closures from switches, pushbuttons, or limit switches. The block can be used with both 2-wire and 3-wire proximity switch inputs. Control power for the block comes from the power line that supplies the inputs. No separate block power supply is needed.

Block features include selectable thresholds and advanced diagnostics.

The block provides configurable detection of Open Wire and Shorted Wire faults. Selectable thresholds extend the use of Open Wire and/or Shorted Wire diagnostics to circuits with many types of input devices and sensors.

  • There are separate On/Off thresholds for each group of eight inputs. On/Off thresholds  are configurable from 25% to 85% of the incoming line voltage, allowing the use of a wide variety of input sensors.

  • Optional Open Wire detection can be selected for individual inputs. The Open/Off threshold can also be configured at 25% to 85% of the incoming line voltage.  Separate Open/Off thresholds can be selected for each group of eight inputs.

  • Optional Short Circuit detection at 10% and 90% of the incoming line voltage can also be selected for individual inputs.

For most applications, the default thresholds and recommended resistor values are not changed.

Fault reporting can also be enabled or disabled circuit-by-circuit.