For on-site repair and support, call us at 1-704-448-2212 or email sales@qualitrol.com.
The GE-Emerson IC695CMM004 PACSystems Rx3i Serial Communications Module provides four independent, isolated serial ports. Up to six Serial Communications modules can be located in the main PACSystems Rx3i backplane.
Each port can be configured for MODBUS Master, MODBUS Slave, CCM Slave, DNP3 Master, DNP3 Slave, or Serial I/O protocol. If any port is configured for DNP3 Master or Slave, the other ports on the module can only be configured for DNP3 Master or Slave.
For modules with firmware version 1.32 or later, half-duplex flow control can be configured using Machine Edition Release 5.90, SP1, SIM 6, or later. Otherwise, flow control defaults to full-duplex.
These modules must be located in an Rx3i Universal Backplane.
We're open Mo-Fr 8:00am to 5:00pm