Overview

Features

  • 0.5 A pilot duty
  • 120/240VAC (50/60Hz) voltage category
  • 74 to 265VAC (47 to 63Hz) operating voltage range
  • Output delay time:
    • OFF to ON:
      • 9.3ms @ 60Hz
      • 11ms @ 50Hz
    • ON to OFF:
      • 9.3ms @ 60Hz
      • 11ms @ 50Hz
  • Current draw:
    • 400mA @ 5.1V
    • 2mA @ 24V
  • 2.1W total backplane power
  • 65W @ 140°F max. power dissipation
  • 22.17 BTU/hr termal dissipation
  • 3mA per point max. off-state leakage current

Description

The Allen-Bradley 1756-OA16 ControlLogix AC Digital Output Module energizes or triggers inductive loads in valves, cylinders, and other solenoid actuated devices. A user-installed interposing circuit is recommended if the module is intended to energize higher inductive loads with high inrush currents. The module is compatible with ControlLogix processors and communication modules, including encompass partner modules. Front panel LED indicators provide channel status. 

In Stock

Part Number Price Available
1756-OA16RMN
$602.28 2 in stock

Interested in Other Part Numbers?

Other part numbers are available to order but are not currently in stock. Current availability for non-stock parts is "Usually ships in 2-3 business days". Click here to select options